Low Delta T 4b2_moe

Low Delta T in District Cooling
View more...
   EMBED

Share

Preview only show first 6 pages with water mark for full document please download

Transcript

Low Delta T ( ∆T) is Far Too Expensive for District Cooling Eric M. Moe IDEA Annual Conference Scottsdale, Arizona June 2007 Common (and Expensive) Myths Energy – Capacity – Complexity - Comfort Myth: Without decoupling buildings or indirect connections, existing (low  ∆T) cooling coils are incompatible with the new (high  ∆T) plant. 12F (6.7C)  ∆T 10F (5.6C)  ∆T 1000 ton customer  45/55F coils (7.2/12.8C) 16F (8.9C)  ∆T chilled water plant 41/57F design (5.0/13.9C) 41F(5.0C) 1500 ton customer  44/56F coils (6.7/13.3C) Reality: Colder water and better control will deliver greater than design  ∆T at peak and part load Energy Labs Coil 5WC-0 806-54x160-A36/6C 80    )   s   n   o    t    ( 70 10.0F (5.6C)  ∆T 60 50    d 41F (7.2C) EWT 16.2F (9.0C)  ∆T   a   o    L 40   g   n 30    i    l   o   o 20    C 45F (5.0C) EWT 19.8F (11.0C)  ∆T Colder CHWST to Coil Increases  ∆T  ∆ T Rises Above Design at Part Load 10 0 0 50 100 150 Flow Rate (gpm) 200 250  Avoid the Expense: Design with cold water and better control to achieve high  ∆T at cooling coils • Design the chilled water plant and distribution for high  ∆T despite low  ∆T cooling coils in buildings • Simplify customer interconnections  – Direct connect if possible, HEX if required  – Maintain the supply water temperature to coils  – Avoid return water temperature control • Rely on (high quality) pressure independent control  – Achieve high  ∆T performance across coils  – Eliminate balancing, even as a system expands Myth: System performance (including  ∆T) can be optimized at the building interface alone LAT LAT VFD (w/ 2-way & balancing valves) Building level return water  temperature control Decoupling (blending) T HEX (indirect connection) T Flow limiter (balancing) T T Reality: Low  ∆T at coils commonly leads to rising supply water temperature which adversely affects performance for the utility and its customer  82 28 Wet Bulb Outside Air Temperature    ) 72    F   g   e    d    ( 62   e   r   u    t   a   r   e   p   m52   e    T 22    ) 17 Supply Water Temperature To Coils 42 11 6 Supply Water Temperature To Building 32 0 Two Weeks in July 2007    C   g   e    d    (   e   r   u    t   a   r   e   p   m   e    T  Avoid the Expense:  Achieve high  ∆T at coils to reduce total energy use, retain customers, simplify systems, and get paid • For the Chilled Water Utility  – Re-capture lost latent cooling revenue • Eliminate low  ∆T at the loads • Maintain low chilled water supply temperature to coils  – Acquire, satisfy, and retain customers • More comfort, greater efficiency, less equipment, lower costs • For the Connected Customer   – Minimize complexity • Direct connections, HEX if required, no balancing  – Reduce pump and fan energy consumption • Higher  ∆T in building, maintain low supply air temps • Remove pumps if not required Myth: District cooling utilities can’t control what customer’s choose to do within their buildings. • • • • • • • Lowest first cost design Insufficient maintenance, dirty coils Bypasses, 3-way valves, C/S pumps Bad pump, pipe, and valve sizing practice Minimal engineering, oversized equipment Poor chilled water flow control Low leaving air temperature Reality: District cooling utilities may develop rate structures that influence customer design and performance $/ton-hr  $0.22 $0.21 $0.20 $0.19 $0.18 $0.17 $0.16 $0.15 ∆T (°F) ≤13 14 15 16 17 18 19 ≥20 ∆T (°C) ≤7.2 7.8 8.3 8.9 9.4 10.0 10.6 ≥11.1 gpm/ton 1.85 1.71 1.60 1.50 chilled water plant design 1.41 1.33 1.26 1.20 It may take a carrot to add a stick to change existing long term contracts! Example: ~ 25,000 ton commercial plant with ongoing (expensive) low  ∆T issues • New plant designed for 10°F (5.6°C)  ∆T - coils have 15°F (8.3°C)  ∆T capability with 40°F (4.4°C) supply • Direct customer connections in original design, no decoupled buildings or heat exchangers • Additional chiller added after startup due to low  ∆T performance in buildings • Utility now has a rate structure that penalizes customers with poor  ∆T performance • Some customers are adding heat exchangers to try to deal with low  ∆T • Rising supply water temperature is creating comfort issues in customer buildings What to Do: Explore common low  ∆T issues relative to coil, distribution, and plant capability • Low return temperature (to the plant) • High supply temperature (to cooling coils) • Where does the excess water go?  –  –  –  – Overflow running chillers Operate additional chillers Blend return water with supply Quickly deplete TES capacity What to Do: Use ARI certified software to fully understand coil capability at peak and part Load Energy Labs 5WC-0 806-36x160-A14/10C Design Conditions (16.0F, 8.9C  ∆T) 120%  Actual Peak Load (21.6F, 12.0C  ∆T) 100%    )    %    (    d   a   o    L   g   n    i    l   o   o    C 80% 60% explore what happens with changes to the entering water  and leaving air temperature conditions 40% 20% 0% 0% 20% 40% 60% Coil Design Flow (%) 80% 100% What to Do:  Assess the economic benefit of correcting low peak and part load  ∆T Example: 12,000 Ton (Growing) Level 1 Trauma Center  “10°F (5.6°)  ∆T Coils with a 16°F (8.9°C)  ∆T Plant”  –  –  –  –  –  –  –  –  –  – Retrofit project Pressure independent control (DeltaPValves), no new coils Reduced gpm/ton by over 60% raising part load  ∆T from 7°F (3.9°C) Removed building pumps and bridges Increased peak load  ∆T from 12 to 16°F (6.7 to 8.9°C) 7,082,381 kWh annual savings (equivalent lbs CO 2 reduced) 53,631 kW reduction at peak (campus has CHP and reverse metering) Increased available system capacity by ~ 3000 tons Improved system reliability and comfort control Eliminated waterside balancing requirements $1,260,000 investment ($105/ton) $708,238 annual savings (plant energy alone) 1.78 years simple payback What to Do: To drive good design, create chilled water contracts that vary with  ∆T performance Example: 4,500 Ton District Cooling (Airport) Customer  “Penalties in contract for less than 18°F (10°C)  ∆T”  –  –  –  –  –  –  –  – New construction project Pressure independent control (DeltaPValves) at coils 38/56°F (3.3/13.3°C) chilled water plant design Thermal storage (ice) is fully utilized to minimize peak load Cold water maintained all the way to cooling coils Customer achieves 20-24°F (11.1-13.3°C)  ∆T at all loads Distribution managed with a single secondary pump in central plant No excess pumping, piping, control, balancing, or heat transfer equipment in the terminal buildings Questions? Eric Moe Flow Control Industries [email protected] Office: 425-483-1297 Cell: 206-890-3266